Tightness Testing And Purging – Flashcards

Unlock all answers in this set

Unlock answers
question
What is A Tightness Test
answer
Impractical and time consuming to test all joints,pipes and connections.
.a localised test to prove the integrity of an installation
.Performed from a single point on the installation,normally at primary meter.
.Uses pressure decay as an indicator to the integrity of an installation.
Pressurise a gas system and isolate the pressure source.
provided there is no leakage of gas.
the pressure will remain constant over a calculated period of time.
If gas leak is present,the pressure within the system would start to decay.
Pressure decay is recognised by a pressure drop on the gauge relative to the severity of the leak.
question
Test Equipment Used
answer
.Pressure Gauge-either water or electronic.
.Testing Tee (where required if testing with air).
Aspirator to pressurise the system where air is used as the test medium.
question
Installation Volume
answer
IV=IVm+IVp+IVf
question
IGEM/UP/1B Edition 3
answer
Any gas installation with LPG/Air,Natural Gas or LPG where the MOP does not exceed 2bar
Pipework upto 35mm
U16/G10 Meters
Max badged capacity does not exceed 16m3/h
question
Tightness Test
answer
Uses pressure decay as an indicator to the integrity of an installation.
question
Purge Volume
answer
(PV)m3=1.5x(IV)m3
question
Water Gauge
answer
Must be capable of reading to at least
0.5mbar
question
Electronic Gauge
answer
Must be capable of being read to at least 0.1mbar
question
No Perceptible Movement
for a water gauge
answer
0.25mbar
question
No perceptible movement
for an electronic gauge
answer
0.2mbar
question
A M.P Let by Test
answer
Carried out between
7 and 10mb
question
A M.P Tightness Test
answer
Carried out between
18 and 19mb
question
Tightness Test Duration
answer
2 Minutes
question
L.P Let by Test
answer
Carried out between
7mb and 10mb
question
L.P Tightness Test
answer
Carried out between
20 and 21mb
question
Tightness Test
New Installations(with or without appliances connected)
will pass if?
answer
No Perceptible Movement and no smell of gas
question
Tightness Test
Existing with NO appliances connected(i.e pipework only)
will pass if?
answer
No Perceptible Movement and no smell of gas
question
Tightness Test
Existing WITH appliances connected
will pass if?
answer
Pressure drop does NOT exceed values in table And No smell of Gas.
question
Tightness Test
<28mm pipe
E6 Meter<6m3>
answer
8mb
question
Tightness Test
<28mm pipe
U6/G4 meter < 6m3/h
pressure drop is..?
answer
4mb
question
Tightness Test
<28mm
U16/G10
>6m3/h <16m3>pressure drop is ?
answer
1mb
question
Tightness Test
>28mm <35mm
E6 Meter<6m3>PRESSURE DROP IS..?
answer
4mb
question
Tightness Test
>28mm <35mm pipe bore
U6/G4 meter < 6m3/h
PRESSURE DROP IS..?
answer
2.5mb
question
Tightness Test
>28mm <35MM
U16/G10
>6m3/h <16m3>pressure drop is ?
answer
1mb
question
Diaphragm U6/G4
Purge volume for
28mm
answer
0.01m3
question
Ultrasonic E6 meter
Purge volume for
28mm
answer
0.01m3
question
Diaphragm U16/G10
Purge volume
<28mm >28mm
answer
1.5 x IVm3
question
Diaphragm U6/G4
Purge volume for
>28mm
answer
1.5 x IV m3
question
Ultrasonic E6
Purge volume for
>28mm
answer
1.5 x IV m3