EPA Section 608 Technician Certification Study Guide – Flashcards

Unlock all answers in this set

Unlock answers
question
What are the typical uses of the center port of gauge set?
answer
Used during evacuation, charging and recovery procedures.
question
What color are the gauges on a manifold gauge set?
answer
Low pressure is blue, High pressure is red.
question
What are the typical ranges of pressure measurements used on the gauges of a manifold gauge set?
answer
High side is 0 to 500 PSIG; Low side is 0 to 350 PSIG and 0 to 30 in. Hg below atmospheric pressure.
question
Is the refrigerant leaving a condenser at a high or low pressure? Is it a liquid or a gas?
answer
High pressure, liquid.
question
Is the refrigerant entering the expansion valve (variable metering device) a liquid or gas?
answer
Liquid, high pressure.
question
Is the pressure of the refrigerant entering the compressor high or low?
answer
Low pressure vapor.
question
Where in a refrigerant circuit does a liquid boil to absorb heat?
answer
In the evaporator.
question
The refrigerant in the suction line is a gas that has been heated above its saturation. What is this condition called?
answer
Superheated vapor.
question
What can cause liquid refrigerant to migrate to a compressor crankcase?
answer
If the compressor is located in the coldest location in the circuit.
question
List two conditions that can quickly damage a compressor that is starting to run?
answer
Operating while in a deep vacuum or when the service valves are closed.
question
What system failures require taking an oil sample?
answer
A compressor burnout or if the unit has had a leak.
question
Is flushing with refrigerant an acceptable tube cleaning method?
answer
No.
question
In addition to preventing and repairing leaks what else should a technician do to conserve refrigerant?
answer
Recover and recycle used refrigerants.
question
What factors affect the speed of an evacuation?
answer
Pump size, hose length, hose diameter, size of system to be evacuated, ambient temperature, suction line size, and the amount of moisture in the system.
question
How should gauge set hoses be sized for use in evacuating a system?
answer
Use the shortest length and the largest diameter possible for the quickest evacuation. At least as large as the vacuum pump inlet.
question
When evacuating what is the benefit of using short hoses with large diameters?
answer
Reduces emissions, pressure drop and evacuation time.
question
Which connection determines the preferred size of hoses used with a vacuum pump?
answer
The vacuum pump inlet.
question
As the capacity and suction hose size increase what happens to the time needed for an evacuation?
answer
Time is reduced.
question
What purpose is served by heating a system during dehydration?
answer
To speed up moisture removal.
question
Does a thorough evacuation remove moisture from a system?
answer
Yes.
question
What can happen to oil in the compressor if the moisture is left in an operating system?
answer
The oil will form hydrofluoric and hydrochloric acids which will corrode the internal parts of the system.
question
What is the result of over-evacuating a system?
answer
No damage will be done.
question
How can a system be leak checked using a low pressure gauge?
answer
Vacuum reading will rise when vacuum pump is turned off.
question
How close should the vacuum gauge be connected to the vacuum pump during evacuation?
answer
As far away as possible.
question
When measuring the vacuum of a system being evacuated the system must be isolated. What must be done to the vacuum pump?
answer
Turn it off and valve it off.
question
What is ozone?
answer
3 atoms of oxygen. It blocks much of the harmful ultraviolet radiation (uv-b) emitted from the sun and it keeps our earth's temperature stable.
question
How much ozone can a chlorine atom destroy in the stratosphere?
answer
One atom can destroy 100,000 ozone molecules.
question
What is Ozone Depletion Potential (ODP)?
answer
The ability of any chemical to deplete the ozone layer.
question
What is CFC?
answer
Chlorofluorocarbon.
question
Which refrigerants are CFC's?
answer
R-11,12,113,114.
question
Which chemical in the CFC refrigerants does the most damage to the ozone layer?
answer
Chlorine.
question
What is an HCFC?
answer
Hydrochlorofluorocarbons.
question
Which refrigerants are HCFC's?
answer
R-22,123.
question
Which is more harmful to the ozone layer a CFC or an HCFC?
answer
CFC's.
question
What is it about CFC's that make them more harmful to the stratosphere?
answer
Chemical strength, they will not breakdown in the lower atmosphere.
question
What is an HFC?
answer
A fluorocarbon that contains no chlorine.
question
Which refrigerants are HFC's?
answer
R-134a,404a,407c,410a.
question
What is the ODP of the HFC refrigerant?
answer
Zero.
question
Which refrigerants contain chlorine?
answer
CFC's and HCFC's.
question
Which refrigerants have high ODP?
answer
CFC's.
question
Which refrigerants have low ODP?
answer
HCFC's, HFC's are zero.
question
What is an azeotrope refrigerant?
answer
A mixture of two or more compounds where the mixture behaves like a single chemical.
question
Is one of the components of R-500 a CFC?
answer
Yes
question
Does stratospheric ozone help or hurt the work of the earth's protective shield?
answer
It helps.
question
What chemical in the stratosphere tells us ozone depletion is occurring?
answer
Chlorine-monoxide.
question
How do we know the chlorine in the stratosphere is coming from CFC's?
answer
The increase in chlorine and fluorine present in the stratosphere, matches the increase in emissions of CFC's.
question
How do we know CFC's get to the stratosphere?
answer
From high altitude air sampling measurements.
question
What role does the ozone layer play in protecting the earth?
answer
It blocks much of the harmful ultraviolet radiation (uv-b).
question
What are the effects on health from increased ultraviolet radiation?
answer
Skin cancer, cataracts, human immunity is reduced.
question
What are the effects on the environment?
answer
Timber growth is reduced, crop yields lowered, marine life and the food chain are impaired.
question
Is ozone depletion a problem for the United States only or a global problem?
answer
A global problem.
question
What is the Montreal Protocol?
answer
A treaty that called for the reduction of production of CFC's.
question
The Montreal Protocol calls for the regulation of what chemicals?
answer
Ozone depleting compounds, CFC's, HCFC's, and Halons.
question
On what date was the production and importation of all CFC's phased out?
answer
In the U.S., after December 31, 1995.
question
Where will we get replacements?
answer
Through recovery of existing refrigerants.
question
What steps are called for by the Clean Air Act?
answer
Taxes on production and use, standards set for the recovery of refrigerants.
question
What is prohibited by the Clean Air Act?
answer
Venting.
question
Do state and local laws have priority over federal law? Can they be less strict?
answer
No. Cities or states can create their own laws but they must be at least as strict as federal laws.
question
To prevent damage to the ozone layer the U.S. is making laws to capture the CFC's now in use. What else does the new law do to restrict the release of CFC's?
answer
Allows states and municipalities to create their own laws to prevent and monitor the release of CFC and HCFC materials into the atmosphere.
question
By recovering refrigerants we ensure adequate supplies and prevent venting. What else does the recovery of refrigerants accomplish?
answer
Prevents stratospheric ozone depletion.
question
The Clean Air Act phases out CFC/HCFC production and prohibits venting. What else does it require?
answer
Standards to be set for recovery of all refrigerants prior to appliance service and disposal.
question
Falsifying or failing to keep required records failing to reach required evacuation levels and knowingly releasing CFC or HCFC refrigerants, are a violations of the Clean Air Act. What activity with a substitute refrigerant is also a violation?
answer
Knowingly venting CFC's, HCFC's and their substitutes.
question
Which refrigerants must be recovered prior to opening a system?
answer
All refrigerants as of 11-15-1995.
question
What releases of a CFC and HCFC are violations of the Clean Air Act?
answer
Any knowingly vented refrigerants.
question
On what date did it become illegal to vent CFC and HCFC refrigerants?
answer
July 1, 1992.
question
Which appliances are covered by Section 608?
answer
Any device which contains and uses a class 1 or class 2 substance as a refrigerant and is used for household or commercial purposes.
question
What is the primary reason the EPA requires a service aperture or process stub on all appliances?
answer
For adding or removing refrigerant from the appliance.
question
Who sets the regulations for recovery machines?
answer
EPA.
question
What is a "self-contained" recovery machines?
answer
A recovery machine that has its own compressor to pump refrigerant out of the system.
question
Is HCFC-123 a "low or "high" pressure refrigerant?
answer
Low pressure.
question
Is CFC-12 a "low" or "high" pressure refrigerant?
answer
High pressure.
question
What is the smallest container in which refrigerants may be sold to a Section 608 certified technicians.
answer
20 pounds.
question
What must you do to the refrigerant in an appliance before disposing of the appliance?
answer
Recover refrigerant or verify that the refrigerant was previously recovered.
question
Who is responsible for removing the refrigerant from household refrigerators prior to disposal?
answer
The final person in the disposal chain. (Scrap metal recyclers, landfill owner, etc)
question
What is the penalty for violation of the Clean Air Act?
answer
Fines up to $27,500 per violation per day and possible loss of technician certification.
question
How much is the bounty for information leading to a conviction?
answer
Up to $10,000.
question
What can happen if a technician cannot demonstrate an ability to use recovery or recycling equipment?
answer
May result in revocation of the technician's certification.
question
What is the name of the process that removes refrigerant from a system and stores it without testing or processing?
answer
Recovery.
question
What is the name for the process that removes moisture and acids from refrigerant but does not test the refrigerant?
answer
Recycling.
question
What is the name for the process that removes moisture and acids from refrigerant and also chemically tests the refrigerant?
answer
Reclaim.
question
What must be done with reclaimed refrigerant before it can be legally resold?
answer
Chemically tested to ARI Standard 700, the purity level of factory new refrigerant.
question
What is the preferred instrument for detecting small leaks?
answer
Electronic leak detector and Ultrasonic detector.
question
What is an inert gas typically used in leak detection?
answer
Dry nitrogen.
question
What is typically indicated by a dehydrated system failing to hold a vacuum?
answer
Leaks.
question
What should be done when recovering the refrigerant form a system where the refrigerant has been improperly mixed?
answer
Recover into a separate container.
question
Can mixed refrigerants be reclaimed?
answer
No.
question
What precautions should be taken when recovering refrigerant from systems with multiple service valves?
answer
Insure that liquid is not trapped between service valves.
question
What is the effect of low ambient temperature on the time required to complete a recovery of refrigerant?
answer
Increases recovery time.
question
Technicians must explain to customers that recovery is necessary and it is required by law. What else should the technician tell the customer?
answer
That all professional service personnel are duty bound to follow the law and protect the environment.
question
What is different about any leaks in systems charged with a blended refrigerant?
answer
Because their vapor pressures can vary widely with temperature they leak from a system at uneven rates.
question
What is "temperature glide"?
answer
A family of lines depicting pressure versus temperature curve.
question
What is ternary blend?
answer
A blend of three different refrigerants.
question
How should systems using blended refrigerants be charged?
answer
In liquid form into the high side of the system.
question
Is there a "drop-in" refrigerant for CFC-12?
answer
No.
question
How do you leak check an HFC-134a system with a partial charge (no HFC-134a detector available)?
answer
Recover the remaining 134a and then pressurize the system with nitrogen and a trace charge of R-22 so you can use an HCFC electronic leak detector.
question
What is the preferred oil to be used with HFC-134a?
answer
Polyolester or ester based.
question
Can ester based oils be mixed with other oils?
answer
No.
question
What does "hygroscopic" mean?
answer
Oil that absorbs moisture easily.
question
What lubricant is recommended for use with a ternary blend?
answer
Depends on the blend: For HCFC's-Alkylbenze, For HFC's-Ployolester.
question
Safety glasses and butyl-lined gloves should be worn for what procedures?
answer
When operating recovery or recycling devices and when handling and refilling refrigerant cylinders.
question
What safety component must be used whenever dry nitrogen is used to pressurize a system?
answer
Pressure regulator.
question
Safety rules for technicians such as: no open flame or hot steam near a refrigerant never cutting or brazing a charged refrigerant line, and never using oxygen to purge or pressurize lines, are all important. Which one should a technician follow?
answer
All of them.
question
What is a Material Safety Data Sheet?
answer
A sheet the states the safety ratings and precautions to be taken for use and handling of chemicals.
question
What safety classification within the ASHRAE standard is the most safe?
answer
A1.
question
What is caused by tie inhaling of refrigerant vapors?
answer
Heart irregularities or Asphyxia.
question
What is the major causes of death involving refrigerants?
answer
Oxygen deprivation.
question
What breathing problem can be caused by CFC-12?
answer
Asphyxia.
question
How can ice be removed from a sight glass?
answer
With alcohol spray.
question
What must be done with a badly corroded relief valve?
answer
It must be replaced.
question
Where can you find the allowable test pressure on a system?
answer
Unit data plate.
question
Can oxygen be used to check for leaks? If not why not?
answer
No. Oxygen in the presence of oil under high pressure can be explosive.
question
What is the likely result of heating a recovery cylinder with an open flame?
answer
Refrigerant will decompose into a toxic material, venting of refrigerant in the atmosphere or the tank may explode.
question
What is the primary purpose of a disposable cylinder?
answer
For virgin refrigerant from the manufacturer.
question
To what internal pressure should a disposable cylinder be reduced to for disposal?
answer
Reduced to at least 0 PSIG.
question
Should you ever use a disposable cylinder for refrigerant recovery?
answer
No.
question
To dispose of a cylinder you should be sure all refrigerant is recovered and the cylinder is no longer usable. What else should you do?
answer
Puncture the container before disposal.
question
For safety refrigerant cylinders should not be rusted or damaged and always properly color coded. What additional step should also be taken with these cylinders?
answer
Properly secured at all times.
question
What is the proper color code for recovery cylinders?
answer
Gray with a yellow top.
question
What is the maximum percent by weight that a cylinder may be filled?
answer
80%.
question
What can happen if a cylinder is overfilled?
answer
Hydrostatic pressure could cause the cylinder to explode.
question
List three methods for measuring the fill level of a recovery cylinder.
answer
Floats, thermistor type sensors, and weighing scales.
question
How often must reusable cylinders be hydrostatically tested?
answer
Every five years.
question
Why must only refillable cylinders be used for transport?
answer
Federal code of regulations title 49 (parts 100-177) states this.
question
What must be affixed to a refrigerant cylinder prior to its shipment to a reclaimer?
answer
DOT classification tag.
question
What is the purpose of a DOT classification tag?
answer
For transportation purposes.
question
What is the correct shipping position for a refrigerant cylinder?
answer
In a vertical or upright position with their valves at the top.
question
What is the EPA definition of a small appliance?
answer
Appliances typically charged at the factory with five pounds or less of refrigerant. Refrigerators and freezers designed for home use, room air conditioners, including window and PTAC units, package heat pumps, dehumidifiers, under the counter ice makers, vending machines and drinking water coolers.
question
Does the EPA require the repair of leaks on small appliances?
answer
Repair of leaks on small appliances is not required, but leaks should be repaired whenever possible.
question
What EPA certification type must technicians have to service any appliance that EPA calls a "small appliance"?
answer
Type 1 or Universal.
question
What service aperture may be used on small appliance?
answer
Access tubes or process tubes.
question
What is the name for a fitting used to connect a recovery device to an appliance, which can close to prevent loss of refrigerant form hoses?
answer
Low-loss fitting. (shut-off valve)
question
What is the primary purpose for using hand valves or self-sealing hoses when using a gauge set?
answer
To prevent loss of refrigerant.
question
Which refrigerants must be recovered under Section 608 of the EPA regulations?
answer
CFC, HCFC and HFC refrigerant.
question
Is there a "drop-in" refrigerant for CFC-12?
answer
No.
question
What is the replacement refrigerant for CFC-12 in household refrigerators?
answer
HFC-134a.
question
What can be determined by taking an accurate temperature and pressure reading of a container holding a recovered refrigerant?
answer
Check for non-condensables and the type of refrigerant.
question
When doing a non-condensables check, a recovery cylinder should stabilize in temperature before any readings are taken. Why?
answer
To find the correct pressure for that temperature on a T/P chart.
question
What is the internal pressure of CFC-12 refrigerant stored at 75 deg. F?
answer
77 PSIG.
question
What is the exception to the rule that says that someone servicing and appliance must have at least one self-contained recovery machine available at their place of business?
answer
Only when the person is working on a small appliance.
question
Ammonia hydrogen, and water can be found in the refrigerators in some campers and other recreational vehicles. Should these compounds be recovered with EPA approved recovery equipment?
answer
No.
question
May the nitrogen used for purging or pressurizing a system be vented to the atmosphere?
answer
Yes.
question
When may a technician recover only 80% of the refrigerant in a small appliance?
answer
In a system dependent recovery with a non-operating compressor?
question
May a technician use a passive recovery machine for recovery from a domestic refrigerator?
answer
Yes.
question
What requirements are placed on recovery machines built after November 15 1993?
answer
Must be able to recover 80% of the refrigerant if the compressor is inoperative or 90% if the compressor is operative. Must be EPA certified.
question
When using a recovery machine manufactured after November 15 1993, what percentage of the refrigerant must be recovered in a household refrigerator with an operating compressor? What percentage if the compressor is NOT operating?
answer
80%, 90%.
question
Is a certified technician responsible for future changes in EPA regulations?
answer
Yes.
question
What type of certification is required to purchase CFC and HCFC refrigerants?
answer
Type 1.
question
What must be done with any regulated refrigerant vented from a graduated charging cylinder?
answer
It must be recovered.
question
What first step must you always take before starting a recovery of refrigerant form any equipment?
answer
Check which refrigerant is being used.
question
What is a "system-dependent" recovery machine?
answer
System dependent recovery machines rely on the compressor of the system being serviced, or the pressure of the refrigerant to pump the refrigerant into a recovery drum.
question
Describe a system-dependent (passive) recovery process for small appliances.
answer
Evacuate or cool a cylinder. Connect the high and low hoses to the system. Pull refrigerant into the cylinder with vacuum or the low tank pressure.
question
What two conditions require that you access both the high and low side of the system for refrigerant recovery?
answer
When there is an inoperative compressor on the system or when necessary to reach required recovery levels.
question
What are the benefits of accessing the low and high side access valves when recovering refrigerant from a system with an inoperative compressor?
answer
It speeds up recovery, improves efficiency and may be necessary to reach required recovery levels.
question
How should you access the system and should you run the compressor when using a system-dependent (passive) recovery on a refrigerator with an operable compressor?
answer
Access the high side and run the compressor.
question
Which access valve (s) should you connect to when recovering from a system with an operating compressor and a completely restricted capillary tube?
answer
High side valve.
question
When using a self-contained (active) recovery device what two conditions can cause excessive pressure on the recovery machine's high side?
answer
A recovery container that is not properly evacuated or one that has unopened valve.
question
Why should defrost heaters be turned on during a recovery from a small appliance?
answer
To speed up refrigerant release from the oil.
question
When should entrapped refrigerant from oil be recovered?
answer
Any time oil is removed from a large system and on small appliances when using system dependent recovery with a non-operating compressor.
question
What does striking the appliance compressor do during a recovery?
answer
Helps to free refrigerant that may be trapped in the oil.
question
A recovery machine should be checked daily for what?
answer
Refrigerant leaks.
question
Can a standard vacuum pump be used as a recovery machine?
answer
In theory yes, but unlikely. First it would have to be certifiable, second it would have to be connected to a non-pressurized recovery container.
question
Should technicians ever mix refrigerants in the field?
answer
No.
question
How should you recover refrigerant that is different from the refrigerant you usually recover?
answer
Different refrigerants must be placed in recovery vessels containing the same type of refrigerant.
question
What can a reclaimer do with any mixed refrigerant you ship to them?
answer
They may either refuse to process and return it at owner's expense or agree to destroy the refrigerant for a substantial fee.
question
To ship recovered refrigerant you must label the container and complete all necessary paperwork. What else should you do?
answer
Use DOT approved cylinders.
question
What federal agency sets the standards for portable refillable tanks or containers used to ship CFC or HCFC refrigerants?
answer
Department of Transportation (DOT).
question
Safety glasses and butyl-lined gloves should be worn fro what procedures?
answer
When you are connecting and disconnecting hoses.
question
Piercing valves are used for what purpose?
answer
To allow access to the sealed system for recovery.
question
On what materials are piercing valves used?
answer
Copper or aluminum refrigerant lines.
question
What should be done to a piercing type Schrader valve after it is installed on a charged system?
answer
It should be capped after any service procedure.
question
Why should solder-less type piercing valves be removed after completion of repairs?
answer
To prevent leaks.
question
What are the critical maintenance checks done to a Schrader valve?
answer
Periodically checked for leaks and replaced if damaged.
question
What does a pungent odor detected after opening a system mean?
answer
It might mean acids are present due to a compressor burnout.
question
What do you do if the oil is contaminated?
answer
Tubing flushing might be required.
question
What system pressure would indicate a recovery should not be performed?
answer
0 PSIG.
question
What are the current methods used to monitor the 80% fill level in a recovery tank?
answer
Floats, thermistor-type sensors and weighing scales.
question
Why do large refrigerant leaks cause suffocation?
answer
Refrigerants will replace air in a confined space leading to possible oxygen starvation.
question
Before entering an area of a large leak of refrigerant what apparatus must be worn?
answer
Self contained breathing apparatus.
question
What should be done if a large leak occurs and no breathing apparatus is available?
answer
Ventilate the space and leave the area.
question
Which acids are formed when refrigerant touches sources of high heat?
answer
Hydrochloric and hydrofluoric acids and phosgene gas.
question
What safety component must be used whenever dry nitrogen is used to pressurize a system?
answer
Nitrogen tanks should be equipped with a regulator.
question
What information does DOT require when shipping refrigerant cylinders?
answer
Shipping papers must indicate the refrigerant type and number of cylinders.
question
Which government agency sets the standards for refillable refrigerant cylinders used to transport CFC and HCFC refrigerants?
answer
Department of Transportation (DOT).
question
What component is always replaced after a a system is opened for service?
answer
Filter-driers.
question
What is the purpose of the moisture indicator in a sight glass?
answer
To permit a check of moisture content in the system.
question
What does "back-seating" a suction valve do?
answer
Allows flow through the main line while closing the access port.
question
What will non-condensables do to the pressures in a refrigerant circuit?
answer
Increase discharge pressure.
question
What causes oil foaming in a system and where does it normally occur?
answer
Oil that is mixed with refrigerant will foam in the compressor crankcase.
question
What system failures require taking an oil sample?
answer
Compressor burnout or if the unit has had a leak.
question
A vacuum pump that is too large can cause what problem?
answer
It can cause moisture to freeze in the system.
question
Where is a receiver typically installed on a system?
answer
At the outlet of the condenser.
question
What will be the boiling temperature of HFC-134a be at 0 PSIG?
answer
-15 degrees F.
question
Is it a requirement that recovery machines contain an oil separator?
answer
No.
question
Which refrigerant is typically used on a residential split system air conditioner?
answer
HCFC-22.
question
Is the refrigerant leaving a receiver a liquid or a gas? Is it at a high or low pressure?
answer
Liquid, high pressure.
question
What is the initial charging method of a system when the charge is specified at 70 pounds?
answer
Charged in liquid state.
question
Is the receiver on the high or low side of a system?
answer
High side.
question
What is the minimum recommended capability (measured in microns) of a vacuum pump used for evacuations?
answer
Should pull a vacuum of 500 microns.
question
What is the pressure of a CFC-12 machine at 72 deg. F while the machine is idle?
answer
73 PSIG.
question
What is the preferred unit of measurement for checking a deep vacuum?
answer
Microns.
question
Where is an accumulator located in a refrigeration system?
answer
On the suction line before the compressor.
question
To prevent freezing of any moisture in a CFC-12 system vapor should first be charged until the pressure is at what level?
answer
33 PSIG
question
What gas should be used during an evacuation to increase pressure to prevent freezing?
answer
Dry nitrogen.
question
What is the purpose of a compressor heater?
answer
To reduce the amount of refrigerant in the lubricating oil.
question
How is moisture remaining from an evacuation removed from the refrigerant in a system?
answer
By the filter-drier.
question
What is the preferred method of leak checking a built-up system prior to charging?
answer
Bubble solution.
question
What would a technician initially look for during a visual inspection of a leaking hermetic system?
answer
Stains around tubing and fittings.
question
What is typically indicated by excessive superheat on a high-pressure system?
answer
Undercharged system, possibly the result of a leaky system.
question
Which refrigerant should be used for a trace charge during leak detection?
answer
R-22.
question
How do you leak check an HFC-134a system with a partial charge (no HFC-134a detector available)?
answer
Recover remaining 134a, pressurize the system with nitrogen and a trace charge of R-22 so you can use an HCFC electronic leak detector.
question
For what purpose are soap bubbles used in leak checking?
answer
For a visual check for leaks.
question
Shaft seals on an open type compressor are susceptible to what failures?
answer
Refrigerant leaks.
question
What leak rate is permissible on industrial and process refrigeration?
answer
Effective 6/14/93, any leak rate of 35% or more on equipment with 50 lbs. of charge or more must be repaired. Less than 35% is permissible.
question
What leak rate is permissible on equipment (other than industrial or process equipment) that contains more than 50 lbs. of refrigerant?
answer
Less than 15% annually.
question
What is the easiest way to check the type of refrigerant used in a packaged rooftop system?
answer
By the equipment data plate.
question
Refrigerant will recover fastest in which phase liquid or vapor?
answer
Liquid.
question
Which refrigerant line should a recovery machine be attached to in order to recover liquid refrigerant from a system?
answer
To the liquid line.
question
After a liquid recovery what must be done with the vapor still in the system?
answer
A vapor recovery must be performed.
question
Recovering in a vapor phase reduces unwanted loss of what?
answer
Oil and unwanted contaminants from the system to the recovery machine and recovery drum.
question
On a high pressure system recovery should the recovery cylinder be heated or cooled?
answer
Cooled.
question
What must be done to a recovery machine when changing to a different refrigerant?
answer
Clean out all residual refrigerant, change oil, replace filters, evacuate machine by pump-out or with another machine.
question
What besides filters must periodically be changed out on a recovery machine?
answer
Oil.
question
Recovered refrigerant can contain oil and acids. Name another compound found in refrigerants?
answer
Moisture.
question
What is the water source for a condensing coil on a water-cooled recovery machine?
answer
Municipal water tap.
question
What access location should you use when recovering from an air cooled system with its condenser several feet above the evaporator?
answer
Suction line.
question
What access location should you use when recovering from a system with its condenser below the evaporator?
answer
Liquid line.
question
Before using a recovery unit
answer
the technician should check service valve positions and check the recovery unit oil level. What additional step must be taken?,All solenoid valves should be open.
question
What is the primary purpose for using hand valves or self-sealing hoses when using a gauge set?
answer
To prevent loss of refrigerant when connecting and disconnecting hoses.
question
What can cause recovery equipment with a hermetic compressor to overheat when drawing a deep vacuum?
answer
No airflow over the compressor body or no suction gas flow over the internal motors, or a combination of the two.
question
What is the reason for not operating a hermetic refrigeration compressor while it is in a deep vacuum?
answer
To prevent overheating the compressor motor.
question
What is the reason for not starting a reciprocating compressor with its discharge service valve closed?
answer
To prevent overheating the compressor motor.
question
When can a "system-dependent" recovery device be used?
answer
On small appliances as long as the device meets EPA standards and the technician adheres to the servicing procedures specified for the recovery equipment. Cannot be used on systems with more than 15 lbs. of refrigerant.
question
What vacuum level must you reach when recovering from a system with 38 pounds of R-502 using a recovery machine manufactured in 1995?
answer
10 inches of Hg.
question
What is EPA's definition of a "major repair"?
answer
Any repair that involves the removal of the compressor, evaporator, condenser, or any auxiliary heat exchanger coil.
question
Prior to making a major repair what vacuum level must you pull when using recovery equipment manufactured in 1996 on a unit with 215 lbs. of CFC-12?
answer
15 inches of Hg.
question
What vacuum level must you pull when using recovery equipment manufactured in 1992 when disposing of an appliance containing 12 lbs. of R-500?
answer
4 inches of Hg.
question
Under what circumstances may a technician recover the CFC refrigerant in an appliance to atmospheric pressure only?
answer
If leaks are in the system or if recovery to target levels would contaminate the refrigerant.
question
What procedure should be performed on an empty recovery cylinder before it is used for storing recovered refrigerant?
answer
It must be evacuated of all non-condensables.
question
What may legally be done with the refrigerant recovered from a system in order to replace a condenser coil?
answer
Reused in the original system or transferred to another system with the same owner after it is checked so that it is free of non-condensables.
question
When servicing an operating unit with a receiver where should the recovery hoses be attached to the unit?
answer
To the liquid line.
question
In order to recover from a system with parallel compressors the individual compressors must be isolated. Why?
answer
It isolates the refrigerant that must be recovered from the rest of the system.
question
Which refrigerant (s) require and equipment room monitor per ASHRAE Standard 15?
answer
All refrigerants.
question
What protection is mandatory to protect a system against damage from excessive pressure?
answer
A pressure relief device.
question
Are multiple relief valves connected in series or parallel?
answer
Parrallel.
question
Why is the use of a regulator required when using dry nitrogen?
answer
To limit the outlet pressure of the nitrogen cylinder.
question
How can ice be removed from a sight glass?
answer
Cleaned with an alcohol spray.
question
How high should you pressurize an idle low pressure chiller to prevent air accumulation?
answer
Slightly above atmospheric pressure.
question
What effect does air in a chiller have on head pressure?
answer
Raises head pressure.
question
What system failures require taking and oil sample?
answer
A leak or major component failure (compressor burnout).
question
Why must water be circulated through a chiller during refrigerant recovery?
answer
To prevent freeze-up of the water as pressure is reduced on the refrigerant.
question
What is the lowest access valve on a low pressure chiller?
answer
The evaporator charging valve.
question
Where is a centrifugal chiller's rupture disk attached?
answer
At the evaporator.
question
What is the typical pressure setting for a low pressure chiller's rupture disk?
answer
15 PSIG.
question
Where is the outlet of a rupture disk discharged?
answer
Outdoor for venting.
question
How is a chiller typically charged?
answer
Liquid through the evaporator charging valve.
question
What minimum saturation temperature needs to be achieved before liquid is charged into a chiller?
answer
Above freezing, typically 36 deg. F.
question
To prevent freezing of water when charging a chiller what pressure should be reached with vapor before using liquid CFC-11?
answer
16.9 inches of Hg.
question
What could result from liquid refrigerant being charged into a chiller that is holding a 29 inch Hg. vacuum?
answer
Can cause system water to freeze.
question
What function is served by a purge unit on a chiller?
answer
Minimize the effects of contamination. To remove non-condensables.
question
What is the most likely cause of air leaks into a chiller refrigerant circuit?
answer
Gaskets and fittings.
question
How is a purge unit connected on a low pressure chiller?
answer
The inlet of the purge unit is typically connected to the top of the condenser.
question
Where is the suction of a purge unit connected?
answer
The inlet of the purge unit is typically connected to the top of the condenser.
question
What is a high efficiency purge unit?
answer
It removes non-condensables that contain a low percentage of refrigerant. This adds to the value of the purge drum in refrigerant containment.
question
Shaft seals on an open type compressor are susceptible to what failures?
answer
Refrigerant leaks.
question
Purge units work best when they are not needed. How can purge unit operating time be reduced?
answer
By regular leak checking and repairing any leaks on a regular schedule.
question
What is the maximum pressure that can be used when leak checking a low pressure chiller?
answer
10 PSIG on low pressure equipment that utilizes a rupture disk.
question
What is the preferred method of leak checking a charged low pressure chiller?
answer
By increasing the refrigerant pressure using an external heat source or running hot water through the chiller tubes not to exceed 10 PSIG.
question
Where should you check for leaks between a chiller refrigerant tube and the water box?
answer
The chiller barrel can be emptied of all water and a leak check can be made at the drain valve with the water off. If the tubes themselves require a leak check, the check can be made with a hydrostatic tube test kit.
question
What is a hydrostatic tube test kit used for?
answer
To check for leaks in a chiller tubes.
question
What leak rate is permissible on industrial and process refrigeration?
answer
Effective 6/14/93, any annualized leak rate of 35% or more on equipment with 50 lbs. of charge or more must be repaired. Less than 35% is permissible.
question
What leak rate is permissible on equipment other than industrial and process equipment?
answer
For appliances with 50 lbs. of charge or more an annual leak rate of 15% or more must be repaired. Less than 15% leak rate is permissible.
question
According to ASHRAE 3-1990 what rise is permitted in vacuum level during a standing vacuum test?
answer
Starting at 1mm of Hg., after 12 hours the vacuum reading should not increase to more than 2.5 mm of Hg.
question
List two steps to reduce the run time of a purge unit.
answer
Regular leak checks and repair any leaks.
question
Why should the water side of the evaporator and condenser be drained before recovering refrigerant from a chiller suspected of having tube leaks?
answer
To prevent moisture form being drawn into the refrigerant circuit.
question
If a purge unit is operating excessively what problem can you expect to find?
answer
Leaks.
question
What condition would cause continuous excessive moisture collection in the purge unit of a low pressure refrigeration system?
answer
Leaks between the refrigerant circuit and the water circuit.
question
Why should oil be warmed prior to removal from a low pressure chiller?
answer
To vaporize any liquid refrigerant that might be trapped in the oil.
question
After liquid recovery what must be done with the vapor still in the system?
answer
Vapor recovery must be performed.
question
Is recovery of refrigerant from a low pressure appliance typically started with liquid or vapor?
answer
Start with liquid removal.
question
Where is the connection made for the water supply used on a water cooled recovery unit?
answer
Local water supply.
question
What should be the maximum pressure on the discharge of a recovery machine for low pressure systems?
answer
10 PSIG, because the rupture disk is set to open at 15 PSIG.
question
What should be done with the water pumps during a recovery form a low pressure chiller?
answer
Term
question
What is EPA's definition of a "major repair"?
answer
Any repair that involves the removal of the compressor, evaporator, condenser, or any auxiliary heat exchange coil.
question
What recovery vacuum must be met on a low pressure appliance using a machine built in 1992?
answer
25 inches of Hg.
question
Why should you wait a few minutes after reaching the required recovery vacuum on an appliance to see if pressure rises?
answer
To see if refrigerant is still trapped in the system.
question
Under what circumstances may the recovery from an appliance be stopped without reaching the prescribed level?
answer
If the recovery would contaminate the refrigerant being recovered. (this level cannot exceed 0 PSIG.)
question
Is it a requirement that recycling and recovery equipment be capable of handling more than one refrigerant?
answer
No.
question
Is it permissible to warm the refrigerant under EPA's regulations to pressurize a low pressure system to do a non-major repair?
answer
Yes.
question
What final vacuum level is required for recovering refrigerant from a low pressure system if the technician is using recovery equipment manufactured BEFORE November 15 1993? AFTER November 15, 1993?
answer
25 inches of Hg, 25 mm of Hg. Absolute (equal to about 29 inches of Hg.)
question
A vacuum pump that is too large for a particular system can cause what problem?
answer
It can cause moisture to freeze in the system.
question
How can you prevent moisture from freezing during dehydration?
answer
You can raise the pressure with nitrogen and allow the ice to melt, then continue with the evacuation.
question
Are multiple relief valves connected in series or parallel?
answer
Parallel.
question
ASHRAE Standard 15 covers refrigerant level monitoring for what refrigerants?
answer
All refrigerants.
question
According to ASHRAE Standard 15 what is the standard for refrigerant concentration for a machine room that must not be exceeded without activating an alarm and starting ventilation in the machine room?
answer
May not exceed the TLV-TWA. (Threshold limit value-Time weighted average.)
question
List four safety procedures that should be followed when working with liquid low pressure refrigerant.
answer
1. Use refrigerant sensors in equipment room. 2. Avoid siphoning refrigerant by mouth. 3. Wear butyl-lined gloves. 4. Wear safety glasses.
question
What is the toxicity and flammability rating of HCFC-123 per ASHRAE Standard 34?
answer
B1.
Get an explanation on any task
Get unstuck with the help of our AI assistant in seconds
New