question
fire department connection
answer
normally on exterior of building... FDNY can pump supplemental water into the sprinkler system, standpipe, or other system furnishing water for fire extinguishment to supplement existing water supplies.
question
system control valve
answer
valve controlling flow to water-based fire protection systems.
question
fire command center
answer
...
question
MFSPC
answer
...
question
MLP
answer
...
question
tags
answer
on closed section valves serving affected areas: area affected, brief description, occupancy classification, c of f number, estimated time until operational
question
Green tag
answer
no impairment found in entire system- main control valve
question
white tag
answer
fully out of service- place on all fire department connecitons
question
red tag
answer
place on main control valve if FULLY OR PARTIALLY out of service... put sprinkler company name, date of removal from service and anticipated time to operational
question
blue disk
answer
partially out of service- on all fire department connections
question
water storage tank
answer
...
question
OS & Y valve
answer
indicating type of control valve used for fire sprinkler system
question
deluge valve
answer
water supply control valve intended to be operated by actuation of an automatic detection system that is installed in the same area as the discharge devices. INTENDED USE IS MANUAL AND AUTO
question
deluge sprinkler system
answer
employing open sprinklers that are attached to a piping system that is connected to a water supply through a valve that is opened by the operation of a detection system installed in the same areas as the sprinklers. WHEN IT OPENS, water flows into the piping system and discharges from all sprinklers attached.
question
Early suppresion fast response sprinklers
answer
fast response sprinkler that is listed for its capability to provide fire suppression of specific high challenge fire hazards
question
extra large orifice sprinklers
answer
= or > 1 inch less pressure to achieve a given discharge density
question
extended coverage sprinkler
answer
400 max square feet discharge
question
fire pump
answer
a provider of liquid flow and pressure dedicated to fire protection. A fire pump is a part of a fire sprinklers system water supply and can be powered by electric, diesel or steam. connected to public water source or tank. provides higher pressure to sprinkler system
question
Glass bulb sprinkler
answer
operated by heat breaking a glass bulb filled with a non freezing liquid with diameters that vary form 3 mm for quick response to 5 mm for standard response
question
hose valve
answer
valve to additional hose connection
question
hydraulic placard
answer
sign attached to a hydraulically calculated sprinkler system indicating the design density, required gallons per minute and pressure for the system to operate properly
question
hydraulically calculated systems
answer
method of sizing auto sprinkler piping using a prescribed amount of water to be distributed over a specific area.
question
impairment coordinator
answer
in charge of safety during out of service systems
question
intermediate level sprinkler
answer
sprinkler equipped with integral shields to protect the operating elemtn form discharge from sprinklers installed at higher elevations
question
large orifice sprinkler
answer
sprinkler head with orifice size equal or greater than 3/4 and less than 1 inch
question
listed device
answer
A fire protection component that has been tested to perform under parameters specified for its use by a nationally recognized testing agency. Underwriter's Laboratory (UL) and Factory Mutual (FM) are the two most common.
question
Master Pressure Reducing Valve
answer
A pressure reducing valve installed to regulate pressures in an entire fire protection system and/or standpipe system zone.
question
Main Drain
answer
The primary drain connection located on the system riser and also utilized as a flow test connection.
question
Microbiologically Influenced Corrosion (MIC)
answer
Corrosion caused by the presence of microbes in the water supply that over time attack the interior of metallic piping and cause leaks, pitting, and blockages.
question
Old-Style/Conventional Sprinkler
answer
A sprinkler that directs 40% to 60% of the water initially in a downward direction and is designed to be installed with the deflector in either the upright or pendent position.
question
Pendent Sprinkler
answer
A sprinkler designed to be installed in such a way that the water stream is directed downward against the deflector.
question
Pintle Screws
answer
A visual indicating device required for sprinklers manufactured prior to 1999 identifying small orifice sprinklers and large orifice sprinklers where orifice size is different than the nominal thread size of the sprinkler head.
question
Pipe Schedule Systems
answer
A method of sizing piping based upon the number of sprinkler heads and the occupancy of the protected area.
question
Preaction Sprinkler System
answer
A sprinkler system employing automatic sprinklers that are attached to a piping system that contains air that may or may not be under pressure, with a supplemental detection system installed in the same areas as the sprinklers.
question
Pressure Control Valve
answer
A pilot operated pressure reducing valve that may be used with a fire or booster pump designed for the purpose of preventing the incoming water supply pressure from dropping below a set pressure.
question
Pressure-Reducing Valve
answer
A valve designed for the purpose of reducing the downstream water pressure under both flowing (residual) and nonflowing (static) conditions.
question
Pressure Relief Valve
answer
A valve designed for the purpose of releasing excess air or water pressure from the Fire Protection Piping System.
question
Pressure Tank
answer
A tank using air pressure to supplying water for water-based fire protection systems. Tank contents to be maintained at one third air to two thirds water.
question
Quick Response Sprinkler Head
answer
A sprinkler having a fusible link with a response time index (RTI) of 50 or less.
question
Recessed Sprinkler
answer
A sprinkler in which all or part of the body, other than the shank thread, is mounted above the ceiling.
question
Residential Sprinkler
answer
A type of fast response sprinkler that has been specifically tested to enhance survivability in the room of fire origin and listed for use in dwelling units.
question
Response Time Index (RTI)
answer
A measurement of the thermal sensitivity of a sprinkler head expressed in (meters-seconds) 1/2.
question
Supervisory signal
answer
A signal indicating the need for action in connection with the supervision of guard tours, fire extinguishing systems or equipment, fire alarm systems or the maintenance features of related systems.
question
Small orifice sprinklers
answer
A sprinkler head with and orifice size smaller than 1⁄2"
question
Solder Link Sprinkler
answer
A sprinkler operated by the melting of a metal link, they vary in size and configuration for quick response and standard response sprinklers. The smaller the size of the link, the faster the sprinkler operates.
question
Spray Sprinkler
answer
A type of sprinkler listed for its capability to provide fire control for a wide range of fire hazards. The most commonly used sprinkler since 1953.
question
Standard Response Sprinkler Head
answer
A sprinkler having a fusible link with a response time index (RTI) of 80 or more.
question
Supervisory signal-initiating device
answer
An initiating device, such as a valve supervisory switch, water level indicator, or low-air pressure switch on a dry-pipe or pre-action sprinkler system, that triggers a supervisory signal.
question
Testing
answer
A procedure used to determine the status of a system as intended by conducting periodic physical checks on water based fire protection systems such as waterflow tests, fire pump tests, alarm tests, and trip tests of dry pipe, deluge, or preaction valves. These tests follow up on the original acceptance test at intervals specified in the appropriate chapter of NFPA #25, 2002 edition.
question
Upright Sprinkler
answer
A sprinkler designed to be installed in such a way that the water spray is directed upwards against the deflector.
question
Water Spray Fixed System
answer
A special fixed pipe system connected to a reliable fire protection water supply and equipped with water spray nozzles for specific water discharge and distribution over the surface or area to be protected. The piping system is connected to the water supply through an automatically or manually actuated valve that initiates the flow of water. An automatic valve is actuated by operation of automatic detection or manual release equipment installed in the same areas as the water spray nozzles. (In special cases, the automatic detection system may also be located in another area.)
question
PREACTION SPRINKLER SYSTEMS
answer
designed for situations where there is danger of serious water damage. Water damage is usually caused by damaged sprinklers or broken piping. Under normal conditions there is no water in the piping. The air in the piping may or may not be is under pressure. A preaction valve prevents the water from entering the system. The valve is automatically opened when a fire detection system discovers that there is a fire or smoke condition. The preaction valve is tripped by the fire detection system before any of the sprinkler heads open. A supervisory device signals when the valve is opened. The preaction valve can also be operated manually.
question
DELUGE SPRINKLER SYSTEMS
answer
equipped with open sprinkler heads designed to wet down an entire area involved in a fire. This system is needed when there is danger of a fire rapidly spreading throughout the building. The deluge system will slow down the spread of the fire. Deluge systems are suitable for hazardous occupancies. This includes buildings in which flammable liquids or other hazardous materials are handled or stored. The sprinkler heads in the deluge system are open at all times. Under normal conditions there is no water in the piping. The air in the piping is not under pressure. A closed control valve prevents water from flowing into the system. A fire detection device automatically opens the control valve when a fire is identified. A supervisory device signals when the valve is opened. When the valve is opened water flows into the system. The water is then discharged out all of the sprinkler heads. The water control valve may also be opened manually.
question
NON-AUTOMATIC DRY SPRINKLER SYSTEMS
answer
ll pipes are normally dry. Water is supplied when needed by pumping water into the system through the Fire Department connection. Some of these systems are supplied by manual operation of a water control valve and may be equipped with sprinklers with or without fusible links. There are several non-automatic systems: 1) Perforated pipe systems - a single line of piping drilled at intervals for water discharge. These systems are usually found in basements or other areas difficult to reach in fire fighting operations. 2) Open fixed spray nozzles for transformer vaults or other hazardous areas; 3) exterior exposure sprinklers (or window sprinklers) use open sprinkler heads to form an external water curtain on the walls of a building, and 4) Foam supply systems are used for the protection of special hazardous occupancies.
question
Curb Valves
answer
Gate valves of the non-indicating type are provided in water distribution systems. Gate valves allow the sprinkler system to be shut off for repairs or maintenance. Such valves are normally a non-rising stem type. They are operated using a special key wrench. A valve box is located over the valve to keep dirt from the valve. The valve box also provides a convenient access point for the valve wrench to the valve nut. A complete record should be made for each valve in the system. This record should include the exact location, the date it was installed, the make, the direction of opening, number of turns to open, and any maintenance that was performed. The control valve for the building may also be on the outside wall or attached to an upright post, known as a post indicator valve (PIV). The building or section of the building controlled by the valve is usually marked on the post. The position of this valve (open or closed) is shown through a telltale opening in the post. On some posts, a padlock must first be opened to release the operating wrench or wheel handle.
question
Pumper Connections for Fire Department Use
answer
Fire Department connections must always be accessible. Each connection shall be fitted with a lower check valve. The lower check valve prevents the backflow of the private water supply into the Fire Department connection. The figure below shows the main features of a Fire Department connection.
question
Fire Pumps
answer
used as a main water supply source for sprinkler systems. They may also be used in combination with gravity tanks to supply sprinkler system. Fire pumps are designed to take the water from a supply source and then discharge the water into the fire protection system under pressure. The amount of pressure with which the water is discharged from the pump is called the total head. The total head is measured in pounds per square inch (psi). The higher the psi rating of the pump the greater the
question
Waterflow Alarm Valves
answer
The basic design of most water-flow alarm valves is that of a check valve which lifts from its seat when water flows into a sprinkler system. This alarm then starts an audible signal to alert the occupants in the building that the sprinkler system has been activated.
question
Vane type waterflow
answer
Switches have a paddle inserted inside the main supply piping perpendicular to the direction of flow. Upon waterflow, the paddle switch transmits an alarm. Vane type waterflow switches cannot be installed to monitor waterflow in dry pipe sprinkler systems.
question
Alarm Retarding Devices
answer
An alarm check valve that is exposed to changing water supply pressure needs an alarm retarding device. This is required to prevent false alarms when the check valve clapper is lifted from its seat by a temporary pressure surge. Vane type water flow switches sensitivity can also be adjusted to changing water pressures.
question
The Centrifugal Pump
answer
The centrifugal fire pump is the standard pump currently used in fire protection systems. This is the preferred pump because it is reliable, compact, requires low maintenance, and it can be powered by a variety of drivers including: electric motors, internal combustion engines, and steam turbines
question
The Vertical Turbine Pump
answer
A vertical turbine pump is really a modified centrifugal pump that has the capability to draw water from streams, ponds, wells etc. Unlike the standard centrifugal pump, the vertical turbine pump does not need the suction supply to be under pressure for it to operate. Instead it draws the water into the pump by suction. The water is drawn into the pump. When it reaches the rotating impellers the water pressure is increased and then forcefully discharged into the fire protection system.
question
Pump Activation
answer
A fire pump can be started automatically or manually. The pump can be started automatically by an electric controller or an engine controller. These controllers activate the pump when there is a drop of water pressure or water flow in the fire protection system. The controllers are adjusted so that a minor drop in water pressure or minor increase in water flow due to a small leak will not activate the pumps. The controllers for the fire pumps are expensive; require extensive maintenance and periodic testing. Where electric motor drive is used, a standby power generator is sometimes required. If an engine controller is used the appropriate fuel storage tanks should be filled and checked regularly.
question
Pressure Maintenance Pumps (Jockey Pumps)
answer
Pressure maintenance pumps, Some times referred to as jockey, or makeup pumps, are often found on sprinkler systems. These pumps are designed to automatically operate when there is a slight drop in pressure due to the leakage in the system or a pressure surge. The jockey pump restores the pressure in the fire protection system to the desired level. When the drop of pressure in the system greater than the capacity of the jockey pump the fire pump is activated.
question
Booster pumps/special service pumps
answer
Booster pumps are sometimes used in sprinkler systems. They small pumps with limited power are usually located in the basement or taking suction from gravity tanks. The booster pump is used when the water pressure available at the highest sprinkler head does not quite meet the needs of the sprinkler system. This small pump increases the water pressure in the sprinkler system until it reaches acceptable levels. The booster pump should not be confused with the fire pump or the jockey pump.
question
Sprinkler system piping
answer
Branch lines are directly connected to sprinkler heads. Cross mains or loop mains are directly connected to branch lines. Feed mains are directly connected to cross mains or loop mains. Risers are able to supply feed mains or cross mains directly.
question
rti
answer
response time index
question
full flow test
answer
performed every 5 years: 1. open main valve to let debris escape, then close 2. system air a nd water pressrue recorded. 3. relieve pressure by opening inspector test valve (use stopwatch) 4. at dry pipe valve note aire pressure which valve trips an note time 5. at inspectors test note time that water flows steadily. 6. test terminated when clean water flows (shit valve) compare to past tests