R-410a Refrigerant Study Guide – Flashcards

Unlock all answers in this set

Unlock answers
question
R-410A is a Refrigerant, also known as....?
answer
SUVA - 410A....... AZ-20......Puron
question
The cylinder color code for R-410A is...?
answer
Rose
question
HCFC-22 is scheduled for total phase out, by the year?
answer
2020
question
Suction and Discharge pressures for R-410A are how much higher than R-22 Systems?
answer
40% to 70%
question
What is Temperature Glide?
answer
A range of condensing and evaporating temperatures for one pressure.
question
When handling Refrigerants, Technicians should?
answer
Wear approved eye protection and gloves/ Avoid loose fitting clothes.
question
A full Nitrogen Cylinder has a pressure of...?
answer
2500 psig
question
Nitrogen Cylinders should only be moved....?
answer
1) with a protective cap in place 2) with an approved Cylinder cart.
question
Temperature Glide for R-410A is less than...?
answer
0.3 degrees F
question
Why is R-410A a better choice than R-22 Refrigerant?
answer
R-410A is more efficient, uses less energy, and has a lower TEWI
question
Due to it's higher Vapor heat Capacity, what can be said of the Discharge Temperature of R-410A when compared to R-22?
answer
Discharge temperature are lower.
question
Systems using R-410A must use what type of lubricant?
answer
Polyol Ester Oil (POE)
question
What can be said of Polyol Ester Oils?
answer
1) Can cause skin irritation 2) Is Hygroscopic..Draws moisture like a magnet 3) Has improved heat transfer characteristics over the mineral oils
question
How would one remove moisture from a Polyol Ester Oil?
answer
Change the filter drier
question
When installing a liquid line filter dryer on a R-410A system, the dryer must have a pressure rating of how much psig?
answer
600 psig
question
What can be said of true Azeotropic Refrigerant?
answer
Will not fractionate.....Has no Temperature Glide.....Is a single component Refrigerant
question
The closer a blend comes to being a true Azeotropic, what can be said of the Temperature Glide?
answer
The glide in temperature will decrease
question
What can be said, if a Refrigerant blend is Zeotropic, or Near Azeotropic (NARM)?
answer
Leaks may cause a change in the composition of the blend.....It will have a temperature glide....It will Fractionate
question
When charging a system with a blend that is Zeotropic, or Near Azeotropic (NARM), what must always be done?
answer
It has to be transferred from the cylinders as a liquid to avoid Fractionation.
question
What is the negative result of a Near-Azeotropic blend Fractionalizing?
answer
This can cause the components of the blend to leak at uneven rates, due to the varying Vapor Pressures.
question
What could be the result of a blend that has Fractionated, depending on the chemical make-up of the Refrigerant?
answer
The Refrigerant could be flammable.
question
What must be be done to avoid Fractionation of a blended Refrigerant?
answer
The Refrigerant has to be charged as a blended liquid.
question
What can be said of Sub-Cooled liquid stored in the Receiver?
answer
It will lose or gain sub-cooling, depending on the surrounding ambient conditions
question
Why is R-407C a good choice for Retrofitting an R-22 Air Conditioning system?
answer
R-407C temperatures and pressure are similar to that of R-22........None ozone depleting
question
What is the color code for R-407C?
answer
Chocolate
question
What is the disadvantage of R-407C, as compared to R-22?
answer
It has a larger temperature glide.
question
What must be done when calculating Super-Heat with R-407C?
answer
Super Heat must be done using a Dew Point value only.
question
What must be done when calculating sub cooling with R-407C?
answer
Sub cooling must be done using a bubble point value only
question
How is compression ratio calculated?
answer
Absolute Discharge Pressure divided by Absolute Suction Pressure
question
R-407C, also has another disadvantage as compared to R-22. What would be this disadvantage?
answer
It will separate (Fractionate) into it's component Refrigerant.
question
At what pressure does the Low Pressure Switch open on an R-410A?
answer
50 psig
question
At what pressure does the High Pressure Switch open on an R-410A?
answer
610 psig, plus or minus 10 psig
question
How is Refrigerant charged into an operating R-410A system?
answer
It has to be charged into the system as a blended liquid.......It has to be throttled into the Low Side to avoid compressor damage.
question
Some R-410A cylinders are equipped with a Dip Tube. What is the purpose of the Dip Tube?
answer
It allows liquid to be removed with the cylinder in the upright position
question
The manufacturers of R-410A equipment have redesigned their compressors. What was done with the compressors?
answer
The compressors all have increased wall thickness.
question
All service equipment used on R-410A systems, must be capable of doing what?
answer
The equipment must be rated for higher pressures
question
The flow area of a R-410A Metering Device is what in relationship to a R-22 Metering Device?
answer
About 15% smaller
question
At what pressure on a R-410A Manifold Gauge does the High Side pressure go to?
answer
800 psig
question
At what pressure on a R-410A Manifold Gauge does the Low Side pressure go to?
answer
250 psig with a 550 psig retard
question
At what pressure does the Service Hoses have to be rated for, on an R-410A System?
answer
800 psig
question
What is the Compressor Internal Pressure Relief (IPR) settings for an R-410A System?
answer
550 to 625 psig
question
R-410A systems should not be stored at a temperature warmer than what?
answer
125 degrees F
question
What type of leak detector is needed for working with R-410A Systems?
answer
One capable of sensing HFC Refrigerants.
question
What can be said of R-410A Refrigerant if the system develops a leak?
answer
Remaining Refrigerant is OK to use, because R-410A has a low fractionation rate.
question
What type of Recovery Cylinders must be used with R-410A?
answer
DOT 4BA 400...........DOT 4BW 400........both cylinders are rated at a 400 psig burst strength
question
If the R-410A System uses a TXV Valve, what is the Proper method of charging the System?
answer
Sub Cooling
question
If R-410A system uses a Capillary Tube or Fixed Metering Device, What is the proper method of charging the system?
answer
Super Heat
question
Bubbles in a sight glass of R-410A, means the system is low on refrigerant...True or False?
answer
False!!!
question
The Evaporator Coil used with R-410A Systems, needs to meet what requirements?
answer
UL approved design.........Service pressure rating of 235 psig
question
If a large leak of Refrigerant occurs in a enclosed area, what should be done?
answer
Vacate and Ventilate the area
question
What is the proper procedure when working on an Electrical Circuit?
answer
Power has to be shut off.......The panel should be locked and tagged....Technician carries the keys to the lock
Get an explanation on any task
Get unstuck with the help of our AI assistant in seconds
New