EPA Type III
Unlock all answers in this set
Unlock answersquestion
What type of equipment can be worked on with Type III certification?
answer
low pressure
question
The most efficient method of leak checking a charged low-pressure refrigeration unit is to
answer
pressurize the system by the use of controlled hot water or heater blankets
question
When pressurizing a system, do not exceed
answer
10 psig
question
After reaching the required vacuum on an appliance when servicing, moisture is indicated by
answer
multiple rises in pressure over a period of time with increase of pauses between rises
question
EPA required evacuation levels for recovery or recycling equipment manufactured or imported before Nov. 15, 1993 is
answer
25 inches Hg
question
EPA required evacuation levels for recovery or recycling equipment manufactured or imported on or after Nov. 15, 1993 is
answer
25 mm Hg absolute
question
What can be used to pressurize a chiller system before opening the system for a non-major repair?
answer
controlled hot water
question
Refrigerant recovery from a system using R-11 or R-123 starts with
answer
liquid removal and is followed by vapor recovery
question
If a strong odor is detected during the recovery process,
answer
a compressor burn-out may have occurred
question
When installing more than one, pressure relief valves must be installed
answer
in parallel
question
The owner must keep records of refrigerant added during service and maintenance on equipment
answer
with charges of 50 lbs. or greater
question
After all the liquid has been removed from an average 350 ton approximately how much vapor refrigerant remains in the system
answer
100 lbs.
question
When charging a system with a low pressure refrigerant should be introduced as a vapor to raise saturation temperature to a minim of
answer
36 degrees
question
Where is the purge unit located in a low-pressure system?
answer
the top of the condenser
question
In a chiller, air and other noncondensables collect
answer
at the top section of the condenser
question
A rupture disk for low pressure chiller will rupture at
answer
15 psig
question
The Standard for machine room safety is
answer
ASHRAE-15
question
Who establishes the refrigerant safety group standard
answer
ASHRAE
question
A low pressure chiller used for comfort cooling must be repaired if it has an annual leak rate of ____ of the total charge.
answer
15 percent
question
ASHRAE 34 Standard Safety classifies R-134a as
answer
A1
question
Because a low-pressure system operates below atmospheric pressure (in a vacuum),
answer
leaks in the gaskets or fittings will cause air and moisture to enter the system
question
To repair a chiller operating with R-22 the technician
answer
must have a Type II certification
question
What refrigerant has a safety classification of B-1?
answer
HCFC 123 (R-123)
question
During evacuation of systems with large amounts of water, it may be necessary to
answer
increase pressure by introducing nitrogen to counteract freezing
question
When leak testing a low pressure chiller, the maximum pressure to use is
answer
10 psig